Delta DRL-48V240W1EN Lyte II Serisi Din-Rail 240W 48V 5A Power Supply

Output
Output Current 5A
Output Voltage 48V
Output Voltage Range 43.2-52.8 Vdc
Output Voltage Adjustment Range 43.2-52.8Vdc
Output Power 240W
Line Regulation ± 0.5% @ 115Vac & 230Vac
Load Regulation ± 0.5%
PARD < 200mVpp @ 0°C to +70°C
< 600mVpp @ -30°C to 0°C
Start up Time 30ms typ. @ 115Vac & 230Vac
Hold up Time 20ms typ. @ 115Vac (100% load)
20ms typ. @ 230Vac (100% load)
Dynamic Response (Ovenshoot & Undershoot O/P Voltage) ± 10% @ 115Vac & 230Vac input, 10-100% load (Slew Rate: 2.5A/μS, 50% duty cycle @ 5Hz & 10KHz)
Start up with Capacitive 3,000µF Max
Rise Time 30ms typ. @ 115Vac & 230Vac
Input
Input Voltage 100-240Vac
Input Voltage Range 90-264vVac
Nominal Input Frequency 47-63Hz
Input Current 2.5A typ.
Efficiency at 100% load 90.5% typ. @ 230Vac
Max Inrush Current 40A typ.@230Vac
Mechanical
Case Chassis / Cover Aluminum / SGCC
Indicator Green LED (DK OK)
Cooling System Convection
Input Terminal 3 pins (rated 300V/30A)
Output Terminal 4 pins (rated 300V/20A)
Noise Sound Pressure Level (SPL) < 25dBA
Mounting Rail Standard TS35 DIN Rail in accordance with EN 60715
Unit Weight 0.62 kg (1.37 Ib)
Dimensions 123.6 x 40 x 117.2 mm
4.87” x 1.57” x 4.61”
Environment 
Vibration (Operating ) IEC 60068-2-6, Sine Wave: 10Hz to 500Hz @ 19.6 m/s² (2G peak); 10 min per cycle, 60 min for X direction
Shock Test (Operating) IEC 60068-2-27, Half Sine Wave: 10G for duration of 11ms; 1 time in X axis
Operating Temperature -30°C to +70°C (-40°C Cold Start)
Storage Temperature -40°C to +85°C
Power De rating > 40°C de-rate power by 1.67 % / °C @115Vac
> 50°C de-rate power by 2.5 % / °C @230Vac
Operating Humidity 20 to 90% RH (Non-Condensing)
Shock Test (non operating) IEC 60068-2-27, Half Sine Wave: 50G for duration of 11ms; 3 times per direction, 9 times in total
Vibration (non operating) IEC 60068-2-6, Random: 5Hz to 500Hz (2.09G); 20 min per axis for all X, Y, Z direction
Operating Altitude 0 to 5.000 Meters (16,400 ft.)
Pollution Degree 2
Over Voltage Categort II (Compliance to EN 62477-1 OVC III with 2000 meters altitude)
Protections
Overvoltage <64.8V, SELV Output, Latch Mode
Overload / Overcurrent 105 – 150% of rated load current, Auto-recovery
Continuous current limit Mode (Vo>80%)
Over Temperature Latch Mode
Short Circuit Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
Protection Aganist Shock Class I with Primary Earth connection
Reliability
MTBF > 700,000 hrs. as per Telcordia SR-332
I/P: 115Vac & 230Vac, O/P: 100% load, Ta: 25°C
Expected Cap Life Time 10 years (230Vac, 50% load @ 40°C)
EMC
Emission CISPR 32, EN 55032, EN 61000-6-4, AS/NZS CISPR32, EN 61204-3
Compliance to FCC Title 47, EN 61000-6-3: Class B
Immunity EN 55035, EN 61000-6-2
Compliance to EN 61000-6-1
Harmonic Current Emissions IEC/EN 61000-3-2, Class A
Voltage Fluctuation and Flicker IEC/EN 61000-3-3
ESD Immunity IEC 61000-4-2
Radiated Immunity IEC 61000-4-3
EFT IEC 61000-4-4
Surge IEC 61000-4-5
Conducted Immunity IEC 61000-4-6
Magnetic Field IEC 61000-4-8
Voltage Dips IEC 61000-4-11
Component Power Supply for general use EN 61204-3

 